Comparative study of two different measuring methods for corona current pulses |
| |
Institution: | 1. State Key Laboratory of Alternate Electrical Power System with Renewable Energy Sources, North China Electric Power University, Beijing 102206, China;2. Central China Branch of State Grid Corporation of China, Wu Han 430077, China;1. Université de Poitiers (CNRS, ISAE-ENSMA), 86962, Futuroscope, France;2. Toyohashi University of Technology, 7 Toyohashi, 441-8580, Japan;1. PPRIME Institute, CNRS - University of Poitiers – ENSMA, IUT, Angoulême, France;2. CITF, Saint Cybardeaux, France;3. Shoubra Faculty of Engineering, Benha University, Cairo, Egypt;4. University of Sidi-Bel-Abbes, Algeria |
| |
Abstract: | Based on a designed coaxial cylindrical corona discharge platform, this paper compares two methods for the measurement of corona current pulse, namely from cage side and conductor side both at low potential. It is found that the corona pulse can be obtained from both methods and the waveform of the current pulse is highly dependent on the sampling resistor. Then two simplified models are proposed to interpret the experimental results and the relationship between the two measurement methods. It shows that the key point in accurately measuring the corona current pulse is the selection of suitable sampling resistor. |
| |
Keywords: | Corona discharge Corona cage Corona current pulses Measurement Modeling |