共查询到20条相似文献,搜索用时 593 毫秒
1.
2.
3.
L. M. Fisher D. F. Alferov M. R. Akhmetgareev A. I. Budovskii D. V. Evsin I. F. Voloshin A. V. Kalinov 《Physics of Atomic Nuclei》2015,78(14):1654-1657
A resistive switching superconducting fault current limiter (SFCL) for DC networks with voltage of 3.5 kV and nominal current of 2 kA is developed. The SFCL consists of two series-connected units: block of superconducting modules and high-speed vacuum breaker with total disconnection time not more than 8 ms. The results of laboratory tests of superconducting SFCL modules in current limiting mode are presented. The recovery time of superconductivity is experimentally determined. The possibility of application of SFCL on traction substations of Russian Railways is considered. 相似文献
4.
本文的磁偏置高温超导故障限流器(SFCL)是一种新型超导限流器,在系统出现短路故障时,发生失超现象,产生高阻抗限制短路电流,达到一定时间后断开超导单元,再由双分裂电抗器二次限流.当短路电流消失后,自动快速恢复到无阻特性,然后重新合闸投入系统运行.在SFCL并网运行前,要对并网运行中出现相间短路等故障的暂态运行特性进行分析,了解并网运行时的状况.本文利用Matlab/Simulink构建了SFCL的仿真分析模型,包含超导限流单元的等效电路模型和热模型.该模型被接入一个由Matlab/Simulink构建的10kV电力系统模型中,用来仿真SFCL的并网运行特性.仿真结果表明了SFCL在并网运行中的效果,以及相间短路故障下失超电阻、通过电流和超导限流单元温度的变化.同时,在中国国网辽宁电力虎石台对SFCL进行了并网运行试验,得到了相间短路故障下的暂态运行特性和失超恢复时间.本文的仿真分析和试验结果,证明了该SFCL样机具备10kV 并网能力,以及快速响应、逐级限流和快速恢复能力 相似文献
5.
6.
L. M. Fisher D. F. Alferov M. R. Akhmetgareev A. I. Budovskii D. V. Evsin I. F. Voloshin A. V. Kalinov 《Physics of Atomic Nuclei》2016,79(14):1577-1584
A resistive switching superconducting fault current limiter (SFCL) for DC networks with a nominal voltage of 3.5 kV and a nominal current of 2 kA was developed, produced, and tested. The SFCL has two main units—an assembly of superconducting modules and a high-speed vacuum circuit breaker. The assembly of superconducting modules consists of nine (3 × 3) parallel–series connected modules. Each module contains four parallel-connected 2G high-temperature superconducting (HTS) tapes. The results of SFCL tests in the short-circuit emulation mode with a maximum current rise rate of 1300 A/ms are presented. The SFCL is capable of limiting the current at a level of 7 kA and break it 8 ms after the current-limiting mode begins. The average temperature of HTS tapes during the current-limiting mode increases to 210 K. After the current is interrupted, the superconductivity recovery time does not exceed 1 s. 相似文献
7.
通过对三相电压型PWM整流器传统直接功率控制(DPC)引起的开关频率不固定,网侧电流谐波分量高,系统调节时间长等问题的分析,提出一种电压型三相PWM整流器模型预测直接功率控制方法,应用模型预测理论构建目标函数并对目标函数进行求偏导,对下一个采样周期的有功功率和无功功率变化进行预测,将模型预测理论与二阶拉格朗日插值法相结合进行功率修正,实现了有功和无功功率的实际值与预测值的误差最小,并采用空间矢量脉宽调制(SVPWM)产生PWM信号驱动整流器功率开关,实现固定的开关频率;仿真结果表明,本方法具有良好的动态和稳态性能,系统对电感参数的变化不敏感,有效降低了交流测电流总谐波失真(THD),提高了交流侧功率因数。 相似文献
8.
聚变堆主机关键系统综合研究设施(CRAFT)超导磁体电源兼具大电流稳态运行、高功率脉冲运行和瞬态故障抑制能力的需求。换流变压器的短路阻抗与超导磁体电源的特性密切相关。为了优化超导磁体电源的性能,基于交直流系统的参数和换流变压器的等效电路模型,研究了换流变压器短路阻抗与超导磁体电源的输出电压、谐波电流、短路故障电流和无功损耗的关系。短路阻抗越小,超导磁体电源的额定输出电压越高,无功损耗越小,这些特性对CRAFT超导磁体电源的性能有利,但是短路故障电流和谐波电流增加,影响电源的短路故障抑制能力和谐波特性。在CRAFT超导磁体电源换流变压器短路阻抗设计时,首先短路阻抗必须满足直流电源的额定输出电压和故障电流抑制能力,其次,由于CRAFT超导磁体电源是多相变流器,仅产生高次特征谐波电流,含量少便于抑制,因而尽量选择较小的短路阻抗。 相似文献
9.
D. F. Alferov M. R. Akhmetgareev D. V. Evsin I. F. Voloshin A. V. Kalinov L. M. Fisher E. V. Tskhai 《Technical Physics》2018,63(1):26-31
The effect of the rate of the rise in the current to 1700 A/ms on the characteristics of a transition of units of superconducting (HTSC) modules from a superconducting to normal state has been experimentally studied. The units differed by the critical current of the HTSC tape and design. The units of HTSC modules are used as a part of the resistive superconducting fault current limiter (SFCL) for ac and dc grids. The obtained dependences should be taken into account when designing a resistive SFCL. 相似文献
10.
11.
基于双PWM结构,根据系统能量流动分析系统在能量平衡状态和能量不平衡状态下系统各部分间的能量关系,并建立双PWM结构能量数学模型。针对系统输出能量与消耗能量不平衡时造成的直流母线电压波动以及输出功率不匹配的问题,建立关于直流母线电压以及网侧电流d轴分量的约束条件,保证系统能量能够平滑变化。采用约束条件对整流器电压外环以及功率内环进行修正,用以实现整流侧输出能量与逆变侧消耗能量的快速平衡,达到双PWM结构间协调控制的目的。根据仿真结果表明,系统在电机功率突变时,能够实现能量的快速平衡,并且能够减少直流母线电压波动,减少网侧谐波分量和直流侧电容。 相似文献
12.
A novel transient rotor current control scheme of a doubly-fed induction generator equipped with superconducting magnetic energy storage for voltage and frequency support 下载免费PDF全文
《中国物理 B》2015,(7)
A novel transient rotor current control scheme is proposed in this paper for a doubly-fed induction generator(DFIG)equipped with a superconducting magnetic energy storage(SMES) device to enhance its transient voltage and frequency support capacity during grid faults. The SMES connected to the DC-link capacitor of the DFIG is controlled to regulate the transient dc-link voltage so that the whole capacity of the grid side converter(GSC) is dedicated to injecting reactive power to the grid for the transient voltage support. However, the rotor-side converter(RSC) has different control tasks for different periods of the grid fault. Firstly, for Period I, the RSC injects the demagnetizing current to ensure the controllability of the rotor voltage. Then, since the dc stator flux degenerates rapidly in Period II, the required demagnetizing current is low in Period II and the RSC uses the spare capacity to additionally generate the reactive(priority) and active current so that the transient voltage capability is corroborated and the DFIG also positively responds to the system frequency dynamic at the earliest time. Finally, a small amount of demagnetizing current is provided after the fault clearance. Most of the RSC capacity is used to inject the active current to further support the frequency recovery of the system. Simulations are carried out on a simple power system with a wind farm. Comparisons with other commonly used control methods are performed to validate the proposed control method. 相似文献
13.
为承受高电压与高电流等级,电阻型超导限流器的各个无感超导单元间不可避免地要进行串并联,由此会带来单元间失超不同步的问题.本文以单根344S超导带材在100ms的故障时间内,带材温度由92K升至300K时,失超电阻随温度的变化为基础,对两者间的关系进行了拟合.之后,以拟合函数为核心,利用Simulink的库中元件构建了单位长度344S带材的失超电阻模型并将其封装为模块.最后,搭建仿真电路模拟了故障时间内两个串联失超模块不同步失超的过程,仿真了分流电阻对失超不同步的改善并对分流电阻的选取进行了优化分析.结论证实,较小阻值的分流电阻更有利于改善失超特性. 相似文献
14.
15.
16.
对稳态强磁场装置电源所需的直流有源滤波器(DAF)进行了设计,提出了利用PWM及并联有源滤波技术的滤波方案。根据其实际负载特性,通过检测负载端电压,利用PWM控制技术产生DAF所需电流并补偿纹波电流。通过对负载侧的滤波电容进行充、放电来调整负载端电压,从而实现负载电流的低纹波。分析表明,该系统具有良好的快速跟踪性能及对谐波很好的抑制效果。仿真结果表明该有源滤波器的良好性能,尤其对低次谐波的抑制更为明显。实验室研样机验证了所提出方案的可行性。 相似文献
17.
提出了一种基于AC-link的新型电机驱动充电一体化拓扑结构,可以满足电机驱动控制和充电两种工作模式。该拓扑正向工作时驱动电机为电机驱动控制状态、反向工作时给蓄电池充电为充电状态。首先对该新型拓扑结构两种工作模式的工作原理进行详细介绍,采用有效的控制策略并使用Simulink软件搭建仿真模型,对一体化拓扑结构和控制策略进行验证,仿真结果表明,该拓扑工作在充电模式时可以满足电池全部充电阶段的不同电压需求;工作于电机驱动模式,无论是加速过程还是正常工作过程,定子电流均呈现良好的三相正弦形态,并且转速可以达到给定值,从而证明了这种拓扑结构和控制策略的可行性。 相似文献
18.
针对工业用轴流风机,设计了基于DSP2808的智能轴流风机控制器,给出了DSP系统、CPLD系统、驱动电路、功率电路、故障检测与保护电路、单端反激变换器的设计方案。分析了风机调节流量的方法,控制器能够根据温度反馈通过PWM斩波实现风机宽范围无级调速,实现节能;控制器能够接收外部电位计、温度传感器、485总线的转速给定,表决后产生最终的转速给定;控制器具备电机绕组过热、IGBT过热、交流侧过欠压、直流侧过欠压、直流侧过流等故障检测与保护功能。实验结果表明:控制器能够实现风机匀加速软起动及起动与转速闭环之间的平稳过渡,有效降低了风机启动、运行过程的噪声,同时实现了节能。 相似文献
19.
ITER中性束注入器加速极需要一套逆变型直流高压电源系统。该电源采用三相三电平(TPTL)直流变换器作为基本单元,通过占空比控制实现对输出电压的快速调节。针对三相三电平直流变换器在小占空比模式下输出电压纹波大的缺点,提出了一种全新的控制策略。该策略通过协调直流母线电压的大小和逆变器占空比的变化对输出电压进行调节。为了验证新的控制策略的性能,搭建了200 kV/60 A的MATLAB/Simulink仿真模型和400 V/6 A的原理样机。仿真结果和样机实验结果表明,新的控制策略可以实现逆变型高压电源在输出电压快速可调的情况下降低输出电压纹波。 相似文献