首页 | 本学科首页   官方微博 | 高级检索  
     检索      


The optimum fin spacing of circular tube bank fin heat exchanger with vortex generators
Authors:Wanling Hu  Mei Su  Liangcheng Wang  Qiang Zhang  Limin Chang  Song Liu  Liangbi Wang
Institution:1. School of Environmental and Municipal Engineering, Lanzhou Jiaotong University, Lanzhou, 730070, Gansu, China
2. Key Laboratory of Railway Vehicle Thermal Engineering, Ministry of Education of China, Lanzhou Jiaotong University, Lanzhou, 730070, Gansu, China
3. Department of Mechanical Engineering, Lanzhou Jiaotong University, Lanzhou, 730070, Gansu, China
4. School of Chemical and Biological Engineering, Lanzhou Jiaotong University, Lanzhou, 730070, Gansu, China
Abstract:In real application, once the pattern of fin is determined, fin spacing of tube bank fin heat exchanger can be adjusted in a small region, and air flow velocity in the front of the heat exchanger is not all the same. Therefore, the effects of fin spacing on heat transfer performance of such heat exchanger are needed. This paper numerically studied the optimal fin spacing regarding the different front flow velocities of a circular tube bank fin heat exchanger with vortex generators. To screen the optimal fin spacing, an appropriate evaluation criterion JF was used. The results show that when front velocity is 1.75 m/s, the optimal fin spacing is 2.25 mm, when front velocity is 2.5 m/s, the optimal fin spacing is 2 mm, and when front velocity is higher than 2.5 m/s, the optimal fin spacing is 1.75 mm.
Keywords:
本文献已被 SpringerLink 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号