首页 | 本学科首页   官方微博 | 高级检索  
     检索      


Experimental studies on heat and mass transfer performance of a coiled tube absorber for R134a-DMAC based absorption cooling system
Authors:S Tharves Mohideen  S Renganarayanan
Institution:(1) Institute of Road and Transport Technology, Erode, Tamil Nadu, 638316, India;(2) Institute for Energy Studies, Anna University, Chennai, Tamil Nadu, 600025, India
Abstract:Absorber is an important component in vapor absorption refrigeration system and its performance has greater influence in overall efficiency of absorption machines. Falling film heat and mass transfer in an absorber is greatly influenced by fluid properties, geometry of heat exchanger and its operating parameters. This paper presents on the results of experimental studies on the heat and mass transfer characteristics of a coiled tube falling film absorber, using 1,1,1,2-Tetrafluroethane(R-134a) and N-N Dimethyl Acetamide (DMAC) as working fluids. The effects of film Reynolds number, inlet solution temperature and cooling water temperature on absorber heat load, over all heat transfer coefficient and mass of refrigerant absorbed are presented and discussed. Normalized solution and coolant temperature profiles and refrigerant mass absorbed along the height of absorber are also observed from the experimental results. The optimum over all heat transfer coefficient for R-134a–DMAC solution found to be 726 W/m2K for a film Reynolds number of 350. The R-134a vapour absorption rate is maximum in the normalized coil height of 0.6 to 1.
Keywords:
本文献已被 SpringerLink 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏