首页 | 本学科首页   官方微博 | 高级检索  
     


Synchronous fluorescence and excitation emission characteristics of transformer oil ageing
Authors:Deepa Subbiah  Sarathi R  Mishra Ashok K
Affiliation:a Department of Chemistry, Indian Institute of Technology Madras, Chennai 600 036, India
b Department of Electrical Engineering, Indian Institute of Technology Madras, Chennai 600 036, India
Abstract:This paper describes the evaluation of synchronous fluorescence spectroscopy (SFS) and excitation emission matrix fluorescence (EEMF) spectroscopy as means of monitoring transformer oil degradation. When accelerated thermal ageing method is used, the onset of degradation of transformer oil on 17th day and transformer oil with polypropylene and cellulosic paper on 23rd and 27th days is sensitively reflected in the SFS and EEMF fluorescence spectral characteristics.
Keywords:Transformer oil   Synchronous scan fluorescence   Excitation emission matrix fluorescence   Ageing