首页 | 本学科首页   官方微博 | 高级检索  
     检索      


Investigation of a heat transfer augmenter as a fouling cleaner and its optimum geometry in the tube side of a condenser
Authors:SR Yang  JM Wang  GD Zai  RH Kim
Institution:

Northeast China Institute of Electric Power Engineering, Jilin City, China

The University of North Carolina at Charlotte, Charlotte, North Carolina, USA

Abstract:A spiral wire was used to augment the heat transfer inside the tubes of surface condensers or shell-and-tube heat exchangers. A spiral wire with a reinforcing component in the direction of the spiral axis has been investigated as a fouling cleaner on the internal surface of a tube, when it is driven in a reciprocating motion with the help of reinforcing wires. When it stays in the tube, it augments the convective heat transfer. Based on the an experimental investigation, the relationships among the heat transfer, drag, cleaning effectiveness, fouling rates, and geometric variables of the cleaner-augmenter performance were found. The results of the experimental investigations on the cleaner-augmenter and the comprehensive evaluation criterion for the device as a fouling cleaner are presented along with the dimensions of tube diameter, wire diameter, and pitch.
Keywords:heat transfer augmentation  fouling  performance evaluation criterion  condenser  shell-and-tube heat exchanger