A power transmissibility method for assessing the performance of vibration isolation of building services equipment
Authors:CM Mak  Su Jianxin
Institution:Department of Building Services Engineering, The Hong Kong Polytechnic University, Hung Hom, Kowloon, Hong Kong Special Administrative Region, People's Republic of China
Abstract:Force transmissibility is commonly adopted in building services engineering to assess the performance of vibration isolation. However, it neglects the effect of floor mobility on structure-borne sound power transmitted from a vibratory machine to the floor/roof and the interactions among several contact points between the vibratory machine and the floor/roof. The problem that motivated this study is the occasional occurrence of unsatisfactory performance of vibration isolators observed in building services engineering. This problem may be due to the over-simplification of the vibratory problem in the usual definition of the un-damped force transmissibility or isolation efficiency commonly used in engineering practice. In this paper, use of a “power transmissibility”, which includes the effect of floor mobility and the interaction of all dynamic forces transmitted to the floor through the vibration isolators, is proposed.
Keywords:
本文献已被 ScienceDirect 等数据库收录!