首页 | 本学科首页   官方微博 | 高级检索  
     


High-risk region of bird streamer flashover in high-voltage transmission lines
Authors:Yuanxiang Zhou  Hanghai Hu  Xu Xu  Jifeng Cui  Yichao Yuan  Zhenyu Li  Yuan Chen  Deming Yu  Qiong Nie  Xidong Liang  Zhicheng Guan
Affiliation:1. State Key Laboratory of Power Systems, Tsinghua University, Haidian District, Beijing 100084, PR China;2. State Grid Operation Company Limited, Beijing 100031, PR China;3. North China Electric Power Research Institute Co., Beijing 100045, PR China;4. State Grid AC Project Construction Corp., Beijing 10005, PR China;5. Beijing EHV Power Supply Company, Beijing 102401, PR China
Abstract:Bird-caused outages are more common and widespread than generally believed, and greatly threaten the safety of transmission lines. However, few reports are concerned with laboratory research of bird-caused faulting, especially in the case of long air gap insulators. This paper carried out experimental and simulation work on bird streamer flashover of 220 kV insulators. It was found that the radial distance from the insulator axis shows great influence on the bird streamer flashover. Significant is that we also found a high-risk region of bird streamer flashover which can be restricted in an elliptical region located at the center of 220 kV insulator string, the major and minor axes being 500 mm and 250 mm. The processes of flashover due to bird streamer are discussed in detail. Simulation work further demonstrates the existence of the elliptical region of high flashover risk, which is of significance for transmission line protection.
Keywords:
本文献已被 ScienceDirect 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号