首页 | 本学科首页   官方微博 | 高级检索  
     检索      


Prevention criteria of electrostatic ignition by a charged cloud in grounded tanks
Authors:A Ohsawa
Institution:Electrical Safety Research Group, Institute of Industrial Safety, National Institute of Occupational Safety and Health, 1-4-6 Umezono, Kiyose, Tokyo 204-0024, Japan;Instituto de Tecnologma Elictrica, Av. Juan de la Cierva 24 - Parque Tecnolsgico, 46980 - Paterna (Valencia), Spain
Abstract:In this paper, we present the criteria of space charge density and wall electric field required to prevent incendive discharges between a grounded protrusion and a charged cloud in cylindrical tanks grounded of up to ≈1.5 × 105 m3 in volume obtained by numerical investigations with wide ranges in the dimensions of the protrusions and tanks. To obtain such criteria, the thresholds of the charge densities of uniformly charged clouds for initiating a discharge at the tip of protrusions are numerically obtained. Furthermore, the transferred charges and energies of the discharges are estimated to investigate their incendivity. For evaluating the risk with a field measurement, the criterion of the electric fields at the side wall of the tanks for avoiding incendive discharges is also obtained.
Keywords:
本文献已被 ScienceDirect 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏