RSD固态脉冲电源中的罗氏线圈电流检测技术
引用本文:王德玉,王宝诚,邬伟扬.RSD固态脉冲电源中的罗氏线圈电流检测技术[J].强激光与粒子束,2009,21(11).
作者姓名:王德玉  王宝诚  邬伟扬
作者单位:燕山大学 电力电子节能与传动控制河北省重点实验室, 河北 秦皇岛 066004
基金项目:国家自然科学基金重点项目 
摘    要: 介绍了基于高速大功率反向开关晶体管(RSD)的磁压缩固态脉冲电源试验平台,就RSD状态电流及磁压缩脉冲电流的波形特征对检测环节高需求的问题,研究了罗氏(Rogowski)线圈传感头的频率特性,在对比已有传感头信号处理方法的基础上,给出了一种新型结构的自积分与外积分复合式罗氏线圈的设计过程和参数选取方法,在保证传感器具有1 mV/A灵敏度的前提下,将传感器的工作频带从低频拓宽到线圈的自然角频率。给出了二级磁压缩网络放电的负载电流实验波形及RSD开关的触发、导通电流波形,验证了该罗氏线圈传感器能够满足本固态脉冲电源中的RSD开关状态电流高精度检测和负载电流的高频检测要求。

关 键 词:磁压缩固态脉冲电源  反向开关晶体管  罗氏线圈  复合积分器  阻尼  测量带宽
收稿时间:1900-01-01;

Rogowski coil transducer for magnetic compression solid-state pulse power based on Reverse Switched-on dynistor
Wang Deyu,Wang Baocheng,Wu Weiyang.Rogowski coil transducer for magnetic compression solid-state pulse power based on Reverse Switched-on dynistor[J].High Power Laser and Particle Beams,2009,21(11).
Authors:Wang Deyu  Wang Baocheng  Wu Weiyang
Institution:Key Laboratory of Power Electronics for Energy Conservation and Motor Drive of Hebei Province, Yanshan University, Qinhuangdao 066004, China
Abstract:In this paper, high frequency behavior of a Rogowski coil is analyzed. Considering the model of the coil frequency response, the damping ratio based on termination resistor can be used to divide the coil frequency band into three bands: derivation band, proportion band and resonance band. Corresponding outside integrator circuits are built according to characteristics of each band. A novel compound integrator circuit consisted of self-integration, passive RC integration and active RC integration is presented. The compound integrator improves the measurement upper bandwidth limit of transducer to the coil's natural frequency. A transducer using a printing circuit board(PCB) coil of 100 turns is constructed with designed frequency of 10 Hz~17 MHz and sensitivity of 1 mV/A. The transducer is developed to measure magnetic comperession current, reverse switched-on dynistor (RSD) switching current and serial-resanont charger current. Experiment waveforms verify that the transducer operates with both about 30 A/50 Hz grid current and 1 kA RSD switching current of 1 kA/μS.
Keywords:magnetic compression solid-state pulse generator  Reverse Switched-on Dynistor  Rogowski coil transducer  compound integrator  damping ratio  measuring bandwidth