首页 | 本学科首页   官方微博 | 高级检索  
     检索      


The Effect of Heat Exchanger Type on Two-Phase Heat Transfer Coefficient and Pressure Drop
Authors:A A S Alshqirate
Institution:Al-Balqa' Applied University, Alshoubak University College , Jordan
Abstract:Three different types of heat exchangers were tested experimentally to investigate two-phase heat transfer coefficient and pressure drop during the condensation process of CO2 gas. Experimental results revealed that the convection heat transfer coefficient was enhanced by a factor of four due to the existence of porous media and by a factor of seven due to the use of micro-pipes when compared to the normal macro-tubes. The pressure drop was measured and noticed only in porous tubes and micro-pipes, reaching about 17.5 kPa/m and 8.4 kPa/m, respectively. Comparisons between experimental and correlated results were conducted.
Keywords:condensation  micro-pipe  macro-tube  porous media  heat transfer  pressure drop  R744
设为首页 | 免责声明 | 关于勤云 | 加入收藏