首页 | 本学科首页   官方微博 | 高级检索  
     


Reignition phenomena after high-frequency current interruption withshort vacuum gaps
Authors:Weinert   H.
Affiliation:Inst. fur Hochspannungstechnik, Tech. Hochschule Aachen;
Abstract:Based on a large number of measurements of high-frequency (HF) current interruptions in vacuum at small contact gaps (⩽600 μm), the statistical reignition behavior of vacuum switching devices after a HF current zero is investigated. Three types of reignitions can be classified. Statistical evaluation of post-arc current measurements for different parameters at current zero and different HF current ignition processes gives information about the stress of the gap as a result of the transient recovery voltage after a HF current zero (HF-TRV) and the accumulated post-arc charge. Comparing post-arc current values at the beginning of the HF-TRV and at the moment of reignition reveals a production of charge carriers during the recovery interval. Possible reasons for the different types of reignitions are discussed
Keywords:
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号