基于传输线网络的特高压变电站智能组件端口电磁骚扰的建模仿真
引用本文:刘骁繁,焦重庆,崔翔,嵇建飞.基于传输线网络的特高压变电站智能组件端口电磁骚扰的建模仿真[J].重庆大学学报(自然科学版),2016,39(6):49-57.
作者姓名:刘骁繁  焦重庆  崔翔  嵇建飞
作者单位:1. 华北电力大学 新能源电力系统国家重点实验室,北京 102206; 国网江苏省电力公司经济技术研究院,南京 210008;2. 华北电力大学 新能源电力系统国家重点实验室,北京,102206;3. 国网江苏省电力公司电力科学研究院,南京,211103
基金项目:国家电网公司科技项目(JB71-16-008)。
摘    要:随着智能化 GIS 设备的发展,GIS 设备上集成了大量电子设备。GIS 设备开关操作产生的特快速瞬态电磁过程主要经由“传感器—二次电缆—智能组件”这段电路对电子设备产生电磁影响。笔者首先基于传输线网络理论建立了开关操作产生的地电位升对“传感器—二次电缆—智能组件”回路的耦合计算模型,然后通过验证实验证明了计算模型的有效性和准确性,最后对不同屏蔽层接地方式下的各传感器端口和智能组件各端口及端口间的骚扰电压进行了仿真研究。计算结果显示,各骚扰电压受接地方式的影响较大;通过选择合适的接地方式,可以有效地抑制开关操作电磁骚扰。

关 键 词:变电站  GIS  开关操作  地电位升  传输线网络
收稿时间:2016/7/10 0:00:00

Modeling and analysis of disturbance voltage induced on the intelligentelectronic device ports based on the transmission-line network inultra high voltage gas insulated substations
LIU Xiaofan,JIAO Chongqing,CUI Xiang and JI Jianfei.Modeling and analysis of disturbance voltage induced on the intelligentelectronic device ports based on the transmission-line network inultra high voltage gas insulated substations[J].Journal of Chongqing University(Natural Science Edition),2016,39(6):49-57.
Authors:LIU Xiaofan  JIAO Chongqing  CUI Xiang and JI Jianfei
Institution:State Key Laboratory of Alternate Electrical Power System with Renewable Energy Sources, NorthChina Electric Power University, Beijing 102206, P. R. China;State Grid Jiangsu Economic ResearchInstitute, Nanjing 210008, P. R. China,State Key Laboratory of Alternate Electrical Power System with Renewable Energy Sources, NorthChina Electric Power University, Beijing 102206, P. R. China,State Key Laboratory of Alternate Electrical Power System with Renewable Energy Sources, NorthChina Electric Power University, Beijing 102206, P. R. China and State Grid Jiangsu Electric Power Company ResearchInstitute, Nanjing 211103, P. R. China
Abstract:With the development of intelligent GIS equipment, a lot of electronic equipments are integrated on the GIS. The very fast transient electromagnetic disturbance (VFTED) resulted from the GIS switching operation has potential impact on the electronic equipment by the electromagnetic coupling between the VFTED and the circuit of "sensor-cable-intelligent electronic device(IED)". In this paper, a theoretical model based on the transmission-line network was established first to calculated the coupling of the ground potential rise produced by switching operations to the circuit of "sensor-cable-IED". Then the validation of this model was verified when it was used to a simple configuration. Finally, based on this model, the disturbance voltages on the sensor/IED ports and those between the IED ports were calculated and the suppression effectiveness of the grounding of the cable shield layer on the disturbance voltages was investigated. The results show that the grounding modes have great influence on disturbance voltage. By choosing the appropriate grounding mode, electromagnetic disturbance caused by switching operations can be effectively suppressed.
Keywords:substation  GIS  switching operation  ground potential rise  transmission-line network