首页 | 本学科首页   官方微博 | 高级检索  
     


PRESSURE DROP IN DOWNWARD FLOW OF CONDENSING STEAM OVER A HORIZONTAL BUNDLE OF SQUARE PITCHED TUBES
Authors:B. M. Burnside  G. C. Cuthbertson  D. A. McNeil
Affiliation:1. School of Mechanical &2. Production Engineering , Nanyang Technological University , Singapore;3. Faculty of Engineering &4. Technology , Multimedia University , Melaka, Malaysia
Abstract:Pressure drop measurements in a 15-row steam condenser configured with in-line tubes, p/D < 1.33, are described. Pressures from 50 to 100 mb and Remax in the range 1,000-18,000 were imposed. It is shown that pressure loss coefficients for the bundle and for two-row pairs were lower than predictions for equivalent single-phase tests except near the bottom of the bundle. There was some evidence that increase in suction parameter increased this effect in the top rows. Taken together with previous investigations [3, 4], a falling trend of suction effect is evident the more closely packed the tubes are. The discrepancy between these findings and the results of simulation experiments [7] is noted.
Keywords:rotation  cavity  discrete heat sources  electronics cooling