PRESSURE DROP IN DOWNWARD FLOW OF CONDENSING STEAM OVER A HORIZONTAL BUNDLE OF SQUARE PITCHED TUBES |
| |
Authors: | B. M. Burnside G. C. Cuthbertson D. A. McNeil |
| |
Affiliation: | 1. School of Mechanical &2. Production Engineering , Nanyang Technological University , Singapore;3. Faculty of Engineering &4. Technology , Multimedia University , Melaka, Malaysia |
| |
Abstract: | Pressure drop measurements in a 15-row steam condenser configured with in-line tubes, p/D < 1.33, are described. Pressures from 50 to 100 mb and Remax in the range 1,000-18,000 were imposed. It is shown that pressure loss coefficients for the bundle and for two-row pairs were lower than predictions for equivalent single-phase tests except near the bottom of the bundle. There was some evidence that increase in suction parameter increased this effect in the top rows. Taken together with previous investigations [3, 4], a falling trend of suction effect is evident the more closely packed the tubes are. The discrepancy between these findings and the results of simulation experiments [7] is noted. |
| |
Keywords: | rotation cavity discrete heat sources electronics cooling |
|
|