EXPERIMENTAL STUDY OF HEAT TRANSFER FROM A DISCRETE SOURCE TO A CIRCULAR LIQUID JET WITH ANNULAR COLLECTION OF THE SPENT FLUID
Authors:D L Besserman  F P Incropera  S Ramadhyani
Institution:Heat Transfer Laboratory, School of Mechanical Engineering, Purdue University , West Lafayette, Indiana, 47907
Abstract:This study reports an experimental investigation of evaporative heat transfer and pressure drop of R-134a flowing downward inside vertical corrugated tubes with different corrugation pitches. The double tube test section is 0.5 m long with refrigerant flowing in the inner tube and hot water flowing in the annulus. The inner tubes are comprised of one smooth tube and three corrugated tubes with different corrugation pitches of 6.35, 8.46, and 12.7 mm. The test runs are performed at evaporating temperatures of 10°C, 15°C, and 20°C; heat fluxes of 20, 25, and 30 kW/m2; and mass fluxes of 200, 300, and 400 kg/m2s. The experimental data obtained from the smooth tube are plotted with flow pattern map for vertical flow. Comparisons between smooth and corrugated tubes on the heat transfer and pressure drop are also discussed. It is observed that the heat transfer coefficient and frictional pressure drop obtained from the corrugated tubes are higher than those from the smooth tube. Furthermore, the heat transfer coefficient and frictional pressure drop increase as the corrugation pitch decreases. The maximum heat transfer enhancement factor and penalty factor are up to 1.22 and 4.0, respectively.
Keywords:vertical  evaporative  heat transfer  pressure drop  corrugated tube