Experimental and numerical analysis of cylindrical turbulators in a double pipe heat exchanger under turbulent flow conditions |
| |
Authors: | Shiva Kumar K. R. N. Sai Krishna |
| |
Affiliation: | Department of Mechanical and Manufacturing Engineering, Manipal Institute of Technology, Manipal Academy of Higher Education, Manipal, India |
| |
Abstract: | In the present work, the use of cylindrical turbulators in a double pipe heat exchanger has been investigated. Cylindrical fin type of turbulators has been placed circumferentially separated by 90° on the outer side of an inner pipe at a regular pitch. Experimental studies were undertaken for different air flow rates in a turbulent regime whose Reynolds number range between 2500 and 10000. Heat transfer characteristics like Nu and friction factor have been experimentally determined. Parametric studies were conducted by changing the pitch and also the orientation of the turbulators. Nu and friction factor were found to increase as the pitch is reduced. A model with alternatively changed orientation outperformed others by exhibiting highest Nu and reduced friction factor. |
| |
Keywords: | Cylindrical turbulators double pipe heat exchanger heat transfer coefficient numerical modelling turbulent flow |
|