首页 | 本学科首页   官方微博 | 高级检索  
     检索      

适用于EAST快控电源的交流绝缘监测技术
引用本文:黄海宏,曹玉玺,王海欣.适用于EAST快控电源的交流绝缘监测技术[J].核聚变与等离子体物理,2017,37(2):204-209.
作者姓名:黄海宏  曹玉玺  王海欣
作者单位:(合肥工业大学,合肥 230009)
基金项目:国家磁约束核聚变能发展研究专项(2011GB109002)
摘    要:为了保障EAST快控电源系统的稳定运行,提出了一种适用于EAST快控电源的高频高压工作环境的交流绝缘监测技术。此方法利用电阻不平衡桥,通过交替投切电阻造成分压的变化,实时采集电压,计算出绝缘电阻值。搭建了Simulink仿真平台,分别将~220V市电和EAST快控电源输出作为电压输入进行实时绝缘监测仿真分析,波形与预期相符。经过实验验证,新方法能够准确完成220V市电交流输入的绝缘监测,并且在快控电源现场能正常工作,达到绝缘监测的精度要求。

关 键 词:EAST快控电源  高频高压  绝缘监测  不平衡桥  
收稿时间:2016-06-12

AC insulation monitoring technology for EAST fast control power supply
HUANG Hai-hong,CAO Yu-xi,WANG Hai-xin.AC insulation monitoring technology for EAST fast control power supply[J].Nuclear Fusion and Plasma Physics,2017,37(2):204-209.
Authors:HUANG Hai-hong  CAO Yu-xi  WANG Hai-xin
Institution:(Hefei University of Technology, Hefei 230009)
Abstract:In order to ensure the stable operation of EAST fast control power supply, a new AC insulation monitoring technique, suitable for the high-frequency and high-voltage working environment of EAST fast control power supply, was presented. The unbalanced bridge of resistance was applied to cause changes in the partial voltage of the resistances by alternately switching, then voltages were collected real-time, and the value of insulation resistance could be calculated. The simulation platform based on Simulink was built to carry out real-time insulation monitoring analysis with ~220V and output of EAST fast control power supply as voltage input, and the waveforms were consistent with the expected. Through experimental verification, the new method can accurately complete the insulation monitoring of 220V AC input, and can work well in the fast control power supply field, where the accuracy of insulation monitoring is achieved.
Keywords:EAST fast control power supply  High-frequency and high-voltage  Insulation monitoring  Unbalanced bridge  
本文献已被 CNKI 等数据库收录!
点击此处可从《核聚变与等离子体物理》浏览原始摘要信息
点击此处可从《核聚变与等离子体物理》下载免费的PDF全文
设为首页 | 免责声明 | 关于勤云 | 加入收藏