首页 | 本学科首页   官方微博 | 高级检索  
     检索      

三级复叠式制冷系统性能的模拟研究
引用本文:申江,王瑞龙,高文全.三级复叠式制冷系统性能的模拟研究[J].低温与超导,2013,41(6).
作者姓名:申江  王瑞龙  高文全
作者单位:天津市制冷技术重点实验室,天津商业大学,天津300134
摘    要:对R404A/R23/R14三级复叠制冷系统进行模拟,研究了三级复叠制冷循环中间温度的选取对系统制冷系数的影响,比较了R404A/R23/R14与R404A/R23在重叠温区的制冷系数以及不同制冷剂对三级复叠系统制冷系数的影响。结果表明:R404A/R23/R14复叠式制冷循环存在最佳中间温度,最佳温度下的压缩机压比大致相等;在重叠温区内,R404A/R23的制冷系数高于R404A/R23/R14;R404A/R508B/R14、R404A/R508A/R14更适用于做三级复叠制冷系统的制冷剂。

关 键 词:模拟  制冷  三级复叠  制冷剂  匹配

Simulative study on three cascade refrigeration system performance
Shen Jiang , Wang Ruilong , Gao Wenquan.Simulative study on three cascade refrigeration system performance[J].Cryogenics and Superconductivity,2013,41(6).
Authors:Shen Jiang  Wang Ruilong  Gao Wenquan
Abstract:In this paper,three cascade refrigeration system performance was simulated.The affect of the middle temperature of three-cascade refrigeration system on the cooling ciefficient was studied.This paper also compared overlapped temperature range COP of R404A/R23/R14 cycle and R404A/R23 cycle,researched the effect for three cascade refrigeration system performance using different refrigerant.The experimental results show that R404A/R23/R14 cycle has optimum middle temperature while compressor pressure ratio was approximately equal.In the overlap of temperature range,performance of R404A/R23 cycle was superior to that of R404A/R23/R14 cycle.R404A/R508B/R14、R404A/R508A/R14 was better refrigerant for three cascade refrigeration system.
Keywords:Simulation  Refrigeration  Three cascade  Refrigerant  Matching
本文献已被 万方数据 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号