首页 | 本学科首页   官方微博 | 高级检索  
     检索      

应用不同混合工质的自复叠制冷机组性能的理论分析
引用本文:钱文波,晏刚,冯永斌,王维,张英志.应用不同混合工质的自复叠制冷机组性能的理论分析[J].低温与超导,2008,36(10).
作者姓名:钱文波  晏刚  冯永斌  王维  张英志
作者单位:1. 西安交通大学能源与动力工程学院,西安,710049
2. 大连三洋空调机有限公司,大连,116600
摘    要:混合工质的不同直接影响到自复叠制冷机组的各项性能。在给定的工况下分析了R744/R600 a、R744/R290、R744/R134 a、R23/R134 a、R23/R22与R32/R600等混合工质的配比、蒸发器出口温度对机组的冷凝压力、制冷量、压缩机耗功和COP的影响。结果表明:R744/R600 a、R744/R290、R744/R134 a与R32/R600 a的最佳配比为35∶65,R23/R134 a的最佳配比为40∶60,R23/R22的最佳配比为30∶70,其中R744/R290系统的COP值为最大;低沸点组分增大情况下,R744/R290、R744/R134 a与R23/R22机组的制冷量和压缩机耗功随着先增加后减小,但R23/R134 a、R32/R600与R744/R600 a机组的制冷量和压缩机耗功一直增加;在最佳配比情况下,随着蒸发温度的升高,其机组的COP值不断增加,而冷凝压力几乎不变。

关 键 词:自复叠制冷系统  混合工质  配比

The theoretical performance analysis of the application of different mixed refrigerants for the auto-cascade refrigeration unit
Qian Wenbo,Yan Gang,Feng Yongbin,Wang Wei,Zhang Yingzhi.The theoretical performance analysis of the application of different mixed refrigerants for the auto-cascade refrigeration unit[J].Cryogenics and Superconductivity,2008,36(10).
Authors:Qian Wenbo  Yan Gang  Feng Yongbin  Wang Wei  Zhang Yingzhi
Abstract:The different mixed refrigerants directly impact on the performances of the auto-cascade refrigeration unit.This article focused on the impact of both the mixed rate of refrigerant such as R744/R600a、R744/R290、R744/R134a、R23/R134a、R23/R22、R32/R600 and outlet temperature of the evaporator to the condensed pressure,the refrigeration capacity,compressor consumption and COP.It was concluded that the supreme mixed ratio of R744/R600a、R744/R290、R744/R134a、R32/R600a is 65∶35,R23/R134a is 60∶40 and R23/R22 is 70∶30.The system COP of R744/R290 is highest among them.With the increasement of the lower boiling point component,the refrigeration capacity and the compressor consumption of the R744/R290、R744/R134a、R23/R22 units go up first and then down later,however,those of R23/R134a 、R32/R600 、R744/R600a increase all the time;with the rise of the evaporation temperature in the case of the the supreme mixed ratio,the COP of the units continues to go up,whereas the condensed pressure is nearly constant.
Keywords:Auto-cascade refrigeration system  Mixed refrigerant  Mixture ratio