On-line purge and trap gas chromatography for monitoring of trihalomethanes in drinking water distribution systems |
| |
Authors: | Brown Michael A Miller Sarah Emmert Gary L |
| |
Affiliation: | The University of Memphis, Department of Chemistry, Memphis, TN 38152, USA |
| |
Abstract: | ![]() A method using an automated on-line purge and trap gas chromatograph with a dry electrolytic conductivity detector (DELCD) has been developed for monitoring four regulated trihalomethanes in drinking water distribution systems. This analyzer samples trihalomethanes from drinking water by pervaporation through a silicone capillary membrane contained within a gas extraction cell (GEC) followed by preconcentration using an adsorbent trap. Trihalomethanes are subsequently desorbed from the trap onto a capillary column, separated and detected. The analyzer operates in real-time, samples directly from the drinking water distribution system and is fully automated. The optimization, operation, and evaluation of the analyzer and method are discussed. Method detection limits (MDL) are less than 1.0 μg L−1 with acceptable estimates for accuracy, and precision. The results from two on-line monitoring studies in chlorinated and chloraminated distribution systems are presented. The performance of the method is compared directly to United Stated Environmental Protection Agency Method 502.2 and shows a very slight, but acceptable bias. |
| |
Keywords: | Trihalomethanes Drinking water On-line monitoring Gas chromatography Disinfection by-products |
本文献已被 ScienceDirect PubMed 等数据库收录! |
|