Comparison of four quantification methods for the determination of PCB in transformer oils |
| |
Authors: | J.-J. Sauvain L. F. de Alencastro J. Tarradellas R. Camenzind G. Karlaganis C. Vuilleumier |
| |
Affiliation: | (1) Swiss Federal Institute of Technology, Institut de Génie de l'Environnement, CH-1015 Lausanne, Switzerland;(2) Interlabor S.A., CH-3123 Belp, Switzerland;(3) Federal Office of Environment, Forests and Landscape, CH-3003 Bern, Switzerland;(4) Bernische Kraftwerke, CH-3000 Bern, Switzerland |
| |
Abstract: | The analysis of PCB in transformer oils has been achieved with three HRGC/ECD based methods, proposed by the International Electrotechnical Commission (IEC/TC 10), by the Comité Européen de Normalisation (CEN/TC 19/WG 22) and by the Deutsches Institut für Normung (DIN 51 527). The same clean-up, described in the CEN/TC 19/WG 22, has been used for all the samples, allowing a comparison of the quantification procedure only. The total chlorine content has also been determined with X-ray fluorescence. These different methods of quantification are compared and their application for legislative purposes is discussed.Dedicated to Professor Dr Dieter Klockow on the occasion of his 60th birthday |
| |
Keywords: | |
本文献已被 SpringerLink 等数据库收录! |
|