The Effect of Heat Exchanger Type on Two-Phase Heat Transfer Coefficient and Pressure Drop |
| |
Authors: | A. A. S. Alshqirate |
| |
Affiliation: | Al-Balqa' Applied University, Alshoubak University College , Jordan |
| |
Abstract: | Three different types of heat exchangers were tested experimentally to investigate two-phase heat transfer coefficient and pressure drop during the condensation process of CO2 gas. Experimental results revealed that the convection heat transfer coefficient was enhanced by a factor of four due to the existence of porous media and by a factor of seven due to the use of micro-pipes when compared to the normal macro-tubes. The pressure drop was measured and noticed only in porous tubes and micro-pipes, reaching about 17.5 kPa/m and 8.4 kPa/m, respectively. Comparisons between experimental and correlated results were conducted. |
| |
Keywords: | condensation micro-pipe macro-tube porous media heat transfer pressure drop R744 |
|
|