摘    要:为研究输电线路爆破除冰效果及动态特性,进行了50 m孤立档输电线路爆破除冰模型实验,采用人工覆冰方式,通过引爆预设在输电线下侧的导爆索去除部分线路覆冰,测量了爆破除冰过程中三种输电线档中位移和端部动张力,并将爆破载荷简化为三角波载荷,利用有限元软件ABAQUS对实验工况进行了模拟验证;进一步利用模拟方法研究了爆破除冰量为20%时除冰位置对跳跃幅值和动张力的影响。结果表明:对于雨凇,爆破作用只会引起输电线爆破区域的覆冰脱落;爆破除冰时跳跃幅值和动张力幅值均大于相同位置自然脱冰,而随除冰位置的变化趋势与自然脱冰相似;与导线相比,地线光缆的跳跃幅值受爆破作用影响更显著。

关 键 词:输电线  爆破除冰  有限元方法  跳跃幅值  动张力
收稿时间:2020-05-29

Dynamic characteristics of electric transmission lines undergone blasting de-icing
XIE Dongsheng,SUN Tao,SHI Zhuopeng,ZHI Shenglong,SHI Linsheng,LI haitao.Dynamic characteristics of electric transmission lines undergone blasting de-icing[J].Explosion and Shock Waves,2021,41(6):148-156.
Authors:XIE Dongsheng  SUN Tao  SHI Zhuopeng  ZHI Shenglong  SHI Linsheng  LI haitao
Institution:1.State Grid Shanxi Economic and Technical Research Institute, Taiyuan 030002, Shanxi, China2.School of Science, North University of China, Taiyuan 030051, Shanxi, China
Abstract:In order to study the dynamic characteristics of electric transmission lines undergone blasting de-icing and the corresponding de-icing effects, model experiments on the isolated transmission lines with a span of 50 m were carried out. The artificial icing was performed out and the detonating cords preset at the lower sides of the transmission lines were detonated to remove partial ice covers of the transmission lines. The displacements and dynamic tensions of three kinds of transmission lines were measured during blasting de-icing. The blasting load was simplified as a triangular wave load, and the experimental conditions were simulated and verified by the finite element software ABAQUS. Furthermore, the effects of the de-icing positions on the jumping height and dynamic tension were explored when the ice was removed by twenty percent. The results show that for glaze ice, the blasting action can only cause the ice to fall off in the blasting area of the transmission lines. The amplitudes of the jumping and dynamic tension induced by blasting de-icing are greater than those by natural de-icing at the same locations, and their changing trends with de-icing location are similar to those by natural de-icing. Compared with the conductor, the jump amplitudes of the ground wire and the optical cable are more significantly affected by blasting.