Investigation of Heat Pump Efficiency on Zeotropic Refrigerants R32/R134a and R32/R152a |
| |
Authors: | N. N. Mezentseva I. V. Mezentsev |
| |
Affiliation: | 1.Kutateladze Institute of Thermophysics, Siberian Branch,Russian Academy of Sciences,Novosibirsk,Russia |
| |
Abstract: | Results of analysis of thermodynamic cycle efficiency with consideration of nonisothermal nature of phase transition indicate that when using the mixture of R32/R152a (30/70%) in the vapor compression heat pumps, the coefficient of performance is up to 4% higher in comparison with R32/R134a (30/70%). The study shows that in cycles with two-stage compression the coefficient of performance increases by 6.5% as compared to the single-stage process. The value of exergic efficiency of the single-stage cycle is equal to 0.47 for zeotropic mixture of R32/R152a (30/70%), and it is equal to 0.45 for the R32/R134a (30/70%) mixture. Data obtained for the zeotropic mixtures are as effective as those obtained for refrigerant R134a. |
| |
Keywords: | |
本文献已被 SpringerLink 等数据库收录! |
|